CyberPower Rack UPS OL6KRT
-
Mapped Fields:
Inlet: Voltage, Rated Amps, & Current. Outlet: Active Power, Current, Voltage. UPS Outlet: Load Percentage & Source. Battery: Capacity Percentage, Runtime Remaining, Voltage, Seconds On, & Status.
- Traps: Yes
- Created by: Gary Elango
-
Trap mappings:
"WARNING: Utility power failed, transfer to backup mode." "SEVERE:The UPS battery capacity is low than threshold, soon to be exhausted." "SEVERE: The UPS has sensed an overload condition." "WARNING:The UPS has been turned off." "WARNING:The UPS entered sleep mode. Output power will not be provided." "SEVERE:The UPS inner temperature is too high." "WARNING:The UPS has enabled buck, high utility voltage." "INFORMATION:The UPS has started a battery test process." "WARNING:The UPS hardware fault."
- Trap clearing: No
- Plugin Type: structured
- Classification: SNMP
- Tested PowerIQ Version: 6.x
- Certified: Yes
- Certified By: Gary Elango
- Date Created: Monday, 27 August 2018
- License: 1
Download attachments:
- cyberpower_pr5000lcdrtxl5u_rups_structured_noproxy.json (0 Downloads)
View the embedded image gallery online at:
http://addons.sunbirddcim.com/index.php/plugins-top/item/113-cyberpower-rack-ups-ol6krt#sigProId9574aef429