Schleifenbauer/ Daxten Rack PDU

Notes :

We won’t be able to do power control on these devices because it requires two OIDs to be set – sdbDeviceOutSwUnlock and sdbDevOutSwCurrentState.

the outlet name OIDs – sdbDevOutletName – are empty in this walk so there’s not outlet names. 

Try 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.1.{outlet_index} and see if the actual PDU returns names.

  • Mapped Fields:

    Inlet: Active power, voltage, current, app. power, power factor, energy, outlet current, voltage, app.power, & active power

  • Traps: No
  • Created by: Scott Fier
  • Trap clearing: No
  • Plugin Type: structured
  • Classification: SNMP
  • Tested PowerIQ Version: 5.1.3, 5.1.4, 5.2.0
  • Certified: Yes
  • Certified By: Gary Elango
  • Date Created: Wednesday, 30 November 2016
  • License: 1

Download attachments:

Read 2150 times