APC Ultra 5000 Rack UPS

  • Mapped Fields: ups output source, ups output load percentage, battery status, battery capacity percentage, battery runtime remaining, battery current, battery voltage, inlet voltage, outlet voltage, outlet current, outlet active power, outlet apparent power
  • Traps: Yes
  • Created by: Gary Elango
  • Trap mappings: SEVERE Communication to the UPS has been lost. Steps to reestablish communication are in progress, SEVERE The UPS has sensed a load greater than 100 percent of its rated capacity, SEVERE The UPS failed its internal diagnostic self-test, SEVERE The UPS batteries are discharged; if utility power fails an immediate low Battery condition will exist. Sufficient runtime for necessary action cannot be guaranteed, WARNING The UPS has switched to Battery backup power, WARNING The UPS has enabled SmartBoost(TM), SEVERE The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to the load, INFORMATIONAL Communication with the UPS has been established, INFORMATIONAL Utility power has been restored, INFORMATIONAL The UPS passed its internal self-test, INFORMATIONAL The UPS has returned from a low Battery condition, WARNING The UPS has been turned 'off' by the management station, WARNING The UPS is entering 'sleep' mode. Power to the load will be cut off, INFORMATION The UPS has returned from 'sleep' mode. Power to the load has been restored, WARNING The UPS has started its reboot sequence. The UPS will reboot itself at this time, WARNING The dip switch settings on the UPS have been changed, possibly altering UPS performance, SEVERE The batteries of the UPS need immediate replacement, SEVERE One of the contacts on the Environmental Monitor has changed from its default position. The first variable is the contact number that is faulted, INFORMATIONAL A fault on one of the Environmental Monitor contacts has been resolved. The first variable is the contact number that has been resolved, SEVERE UPS on bypass due to internal fault, WARNING:UPS on bypass - user set via software or panel, WARNING:UPS on bypass - initiated by user, INFORMATIONAL:UPS has returned from bypass, SEVERE Base module bypass power supply needs repair, SEVERE Base module fan needs repair, SEVERE Check installation of external Battery packs signal cable, INFORMATIONAL:UPS is communicating with the external Battery packs, INFORMATIONAL:A Battery calibration test has been initiated on the UPS, INFORMATIONAL Agent restarting as commanded by manager, INFORMATIONAL:A UPS is turned on, INFORMATIONAL The overload condition has been cleared, INFORMATIONAL The UPS has returned from SmartBoost(TM), INFORMATIONAL:A bad Battery fault has been cleared, INFORMATIONAL The UPS has finished calibrating, INFORMATIONAL:A UPS discharge condition has been cleared, INFORMATIONAL:A graceful shutdown has been initiated, WARNING The output voltage is not within acceptable range, INFORMATIONAL The output voltage has returned to an acceptable level,
  • Trap clearing: Yes
  • Plugin Type: structured
  • Classification: SNMP
  • Tested PowerIQ Version: 9.x
  • Certified: Yes
  • Certified By: Gary Elango
  • Date Created: Thursday, 11 April 2024

Download attachments:

Read 182 times